Motor Starters for Digital I/O Modules

This appendix provides data to help you choose a ControlLogix digital I/O
module to drive Bulletin 500 series motor starters in your application. The tables
list the number of motor starters (five sizes are listed for each module) that a
particular digital I/O module can drive.

IMPORTANT

When using the tables, remember that the supply voltage for each module
must not drop below the minimum state motor starter supply voltage.

Table 61 - Maximum Allowed 2-3 Pole Motor Starters (120V AC/60 Hz)

Cat. No.

Motor Starters

Size 0…1

Size 2

Size 3

Size 4

Size 5

1756-0A16I

16

15 @ 30 °C (86 °F)
12 @ 60 °C (140 °F)

13 @ 30 °C (86 °F)
10 @ 60 °C (140 °F)

8 @ 30 °C (86 °F)
6 @ 60 °C (140 °F)

5 @ 30 °C (86 °F)
4 @ 60 °C (140 °F)

1756-OA16

16

14 (only 7 per group)

4
(Only 2 per group)

None

None

1756-OA8

8

8

8

8 @ 30 °C (86 °F)
6 @ 60 °C (140 °F)

5 @ 30 °C (86 °F)
4 @ 60 °C (140 °F)

1756-OA8D

8

8

8

None

None

1756-OA8E

8

8

8

6 (only 3 per group)

6 @ 30 °C (86 °F)
(only 3 per group)
4 @ 60 °C (140 °F)
(only 2 per group)

Table 62 - Maximum Allowed 2-3 Pole Motor Starters (230V AC/60 Hz)

Cat. No.

Motor Starters

Size 0-1

Size 2

Size 3

Size 4

Size 5

1756-OA16I

16

16

16

16 @ 30 °C (86 °F)
13 @ 60 °C (140 °F)

11 @ 30 °C (86 °F)
9 @ 60 °C (140 °F)

1756-OA16

16

16

16

4 (only 2 per group)

2 (only 1 per group)

1756-OA8

8

8

8

8

8

Table 63 - Maximum Allowed 2-3 Pole Motor Starters (24V AC/60 Hz)

Cat. No.

Motor Starters

Size 0-1

Size 2

Size 3

Size 4

Size 5

1756-ON8

4 @ 30 °C (86 °F)
3 @ 60 °C (140 °F)

4 @ 30 °C (86 °F)
3 @ 60 °C (140 °F)

None

None

None