Chapter 6
Install ControlLogix I/O Modules
Choose Extended-depth
Housing
There are two housing options you must consider when wiring your
ControlLogix digital I/O module: standard-depth or extended-depth.
When you order an RTB for your I/O module, you receive standard-depth
housing. If your application uses heavy gauge wiring, you can order extended-
depth housing. Extended-depth housing does not come with an RTB.
IMPORTANT
The housings shown are used with a spring clamp RTB, but the capacity for
each remains the same regardless of RTB type.
Cat. No.
RTB Type
Wire Capacity
Number of Wires
1756-TBNH
NEMA clamp
Standard-depth
336 mm
2
(0.52 in.
2
)
36 - 18 AWG wires
23 - 14 AWG wires
1756-TBSH
Spring clamp (20-position)
1756-TBCH
Cage clamp
1756-TBS6H
Spring clamp (36-position)
1756-TBE
Any RTB that uses heavy gauge
wiring
Extended-depth
628 mm
2
(0.97 in.
2
)
40 - 14 AWG wires
Standard-depth Housing
Extended-depth Housing