Rtb wiring recommendations – Rockwell Automation 1756-XXXX ControlLogix Digital I/O Modules User Manual

Page 118

Advertising
background image

118

Rockwell Automation Publication 1756-UM058G-EN-P - November 2012

Chapter 6

Install ControlLogix I/O Modules

The open section at the bottom of the RTB is called the strain relief area. The
wiring from the connections can be grouped with a plastic tie.

RTB Wiring Recommendations

Consider these guidelines when wiring your RTB:

Begin wiring the RTB at the bottom terminals and move up.

Use a tie to secure the wires in the strain relief area of the RTB.

A jumper bar is shipped with certain I/O modules to assist in installation.
For an example of when to use the jumper bar, see the

1756-IA16I

wiring

diagram.

Extra jumper bars can be purchased by ordering catalog number
1756-JMPR.

For applications that require heavy gauge wiring, order and use an
extended-depth housing, catalog number 1756-TBE. For more
information, see

page 120

.

IMPORTANT

Make sure the wire, and not the screwdriver, is inserted into the open terminal
to prevent damage to the module.

Advertising