Diagnostic Module Features
Chapter 4
This feature has a corresponding tag that can be examined in the user program in
the event of a fault. For more information on these tags, see
If an output cannot be verified, a point-level fault is sent to the controller.
Follow these steps to enable the field-side output verification.
1.
On the Module Properties dialog box, click the Configuration tab.
2.
Do one of the following in the Output Verify column:
•
To enable the feature for a specific point, check the corresponding
checkbox.
•
To disable the feature for a specific point, clear the corresponding
checkbox.
3.
Click OK.