Rockwell Automation 1756-XXXX ControlLogix Digital I/O Modules User Manual

Page 77

Advertising
background image

Rockwell Automation Publication 1756-UM058G-EN-P - November 2012

77

Diagnostic Module Features

Chapter 4

This feature has a corresponding tag that can be examined in the user program in
the event of a fault. For more information on these tags, see

Appendix B

.

If an output cannot be verified, a point-level fault is sent to the controller.

Follow these steps to enable the field-side output verification.

1.

On the Module Properties dialog box, click the Configuration tab.

2.

Do one of the following in the Output Verify column:

To enable the feature for a specific point, check the corresponding
checkbox.

To disable the feature for a specific point, clear the corresponding
checkbox.

3.

Click OK.