Rockwell Automation Publication 1756-UM058G-EN-P - November 2012

89

Fast Module Features

Chapter 5

3.

On the New Module or Module Properties dialog box, click the
Configuration tab.

Timestamp fields only appear on the Configuration tab when you choose
Timestamp Data from the Input Data pull-down menu on the Module
Definition dialog box.

4.

Complete the fields as described in the table below and click OK.

5.

If you checked the Latch Timestamps checkbox, use program logic or the
RSLogix 5000 tag editor to acknowledge transitions and clear latched
timestamps via the Pt[

x].NewDataOffOnAck and

Pt[

x].NewDataOnOffAck output tags.

For more information about module tags, refer to

Appendix B

.

Field

Description

Configuration Tag

Enable COS/Timestamps
Off

On

To enable COS and timestamping for an Off to On transition for a
point, check the corresponding checkbox.
To disable COS and timestamping for an Off to On transition for a
point, clear the corresponding checkbox.

Pt[x].COSOffOnEn

Enable COS/Timestamps
On

Off

To enable COS and timestamping for an On to Off transition for a
point, check the corresponding checkbox.
To disable COS and timestamping for an On to Off transition for a
point, clear the corresponding checkbox.

Pt[x].COSOnOffEn

Latch Timestamps

Check the checkbox to latch a CIP Sync timestamp for a COS
transition:
When an initial timestamp is latched, timestamps for

subsequent COS transitions are dropped.

Once a latched timestamp is acknowledged via the

corresponding bit in the Pt[x].NewDataOffOnAck or
Pt[x].NewDataOnOffAck tag, the timestamp is overridden
upon the next COS transition.

IMPORTANT: Timestamps are latched only for points that are
enabled for COS and timestamping.

LatchTimestamps