Rockwell Automation 1756-XXXX ControlLogix Digital I/O Modules User Manual

Page 45

Advertising
background image

Rockwell Automation Publication 1756-UM058G-EN-P - November 2012

45

Common Module Features

Chapter 3

EXAMPLE

In the following scenario, Disable Keying prevents I/O communication.

The module configuration is for a 1756-IA16 digital input module. The physical
module is a 1756-IF16 analog input module. In this case, communication is
prevented because the analog module rejects the data formats that
the digital module configuration requests
.

EXAMPLE

In the following scenario, Disable Keying allows I/O communication:

The module configuration is for a 1756-IA16 digital input module. The physical
module is a 1756-IB16 digital input module. In this case, communication is
allowed because the two digital modules share common data formats.

Module Configuration

Vendor = Allen-Bradley
Product Type = Digital Input Module
Catalog Number = 1756-IA16
Major Revision = 3
Minor Revision = 1

Physical Module

Vendor = Allen-Bradley
Product Type = Analog Input Module
Catalog Number = 1756-IF16
Major Revision = 3
Minor Revision = 2

Communication is prevented

Module Configuration

Vendor = Allen-Bradley
Product Type = Digital Input Module
Catalog Number = 1756-IA16
Major Revision = 2
Minor Revision = 1

Physical Module

Vendor = Allen-Bradley
Product Type = Digital Input Module
Catalog Number = 1756-IB16
Major Revision = 3
Minor Revision = 2

Communication is allowed