Response time, Features specific to fast input modules – Rockwell Automation 1756-XXXX ControlLogix Digital I/O Modules User Manual

Page 85

Advertising
background image

Rockwell Automation Publication 1756-UM058G-EN-P - November 2012

85

Fast Module Features

Chapter 5

Response Time

The tables below indicate the screw-to-backplane response time of fast input and
fast output modules.

Features Specific to
Fast Input Modules

The table below lists features specific to ControlLogix fast digital input modules.

Table 16 - Input Response Time

Delay

Response Time

Total On/Off delay (screw to backplane)

14 μs nom/23 μs max + user-configurable filter time

Hardware delay

< 1 μs nom, 2 μs max

Firmware delay

13 μs nom, 21 μs max

User-configurable filter time

0…30,000 μs

Table 17 - Output Response Time

Delay

Response Time

Total On/Off delay (screw to backplane)

14 μs nom/23 μs max

Hardware delay

< 1 μs nom, 2 μs max

Firmware delay

13 μs nom, 21 μs max

Topic

Page

Pulse Capture

86

Per Point Timestamping and Change of State

87

Software Configurable Filter Times

90

Dedicated Connection for Event Tasks

93

IMPORTANT

In RSLogix 5000 software, version 18.02.00 and 19.01.00, output tag
information is sent to the 1756-IB16IF module only at the RPI rate defined
during configuration. For optimal performance, use an Immediate Output (IOT)
instruction.

For example, the rung shown below contains an IOT instruction for a fast input
module in slot 3. Add a similar rung to your last routine within the Main Task to
mimic normal output tag processing.