Tag Definitions

Appendix B

Table 38 - Standard Output Module Input Data Tags

Name

Data Type

Definition

CSTTimestamp
(8 bytes)

DINT[2]

Coordinated System Time Timestamp—Timestamp of diagnostic input data including fusing (see BlownFuse,
NoLoad, OutputVerifyFault, FieldPwrLoss), which is updated whenever a diagnostic fault occurs or goes away.

Data
(1 bit per point)

DINT

Data—Off/On status for the output point echoed back from the output module. This is used to verify proper
communication only. No field side verification is done. For field side verification, see OutputVerifyFault.
0 = Off
1 = On

Fault
(1 bit per point)

DINT

Fault—This is an ordered status of faults that indicates a point is faulted and I/O data for that point may be incorrect.
Check other diagnostic faults, if they are available, for further diagnosis of the root cause. If communication to the input
module is lost, then all points for the module will be faulted.
0 = No fault
1 = Fault (FuseBlown, NoLoad, OutputVerifyFault, FieldPwrLoss, or CommFault)

FuseBlown
(1 bit per point)

DINT

Fuse Is Blown—An electronic or mechanical fuse has detected a short or overload condition for an output point. All
FuseBlown conditions are latched and must be reset by the user.
0 = No fault
1 = Fault

Table 39 - Standard Output Module Output Data Tags

Name

Data Type

Definition

CSTTimestamp
(8 bytes)

DINT[2]

Coordinated System Time Timestamp—Timestamp to be used with scheduled outputs and coordinated system time
(CST). Used to synchronize outputs across the system by indicating the time (CST timestamp) at which the output module
is to apply its outputs.

Data
(1 bit per point)

DINT

Output Status—On/Off status of the output point originating from the controller.
0 = Off
1 = On

Table 40 - Diagnostic Output Module Configuration Tags

Name

Data Type

Definition

FaultLatchEn
(1bit per point)

DINT

Latch Fault—If enabled for a point, any NoLoad, OutputVerifyFault or FieldPwrLoss stays latched in the faulted state
even if the fault no longer exists until the user clears the fault. This does not affect FuseBlown; it is always latched.
0 = Disable
1 = Enable latching

FaultMode
(1bit per point)

DINT

Fault Mode—Used in conjunction with FaultValue to configure the state of outputs when a communication fault occurs.
See FaultValue.
0 = Use FaultValue (Off or On)
1 = Hold Last State

FaultValue
(1 bit per point)

DINT

Fault Value—Used in conjunction with FaultMode to configure the state of outputs when a communication fault occurs.
See FaultMode.
0 = Off
1 = On

FieldPwrLoss
(1 bit per point)

DINT

Field Power Loss—Enables Field Power Loss diagnostic.
0 = Disable
1 = Enable

NoLoadEn
(1 bit per point)

DINT

No Load—Enables No Load diagnostic.
0 = Disable
1 = Enable

OutputVerifyEn
(1 bit per point)

DINT

Output Verify—Enables Output Verify diagnostic.
0 = Disable
1 = Enable