Rockwell Automation 1756-XXXX ControlLogix Digital I/O Modules User Manual

Page 96

Advertising
background image

96

Rockwell Automation Publication 1756-UM058G-EN-P - November 2012

Chapter 5

Fast Module Features

For more information about defining a Fault mode state, refer to

Configurable

Point-level Output States on page 55

.

Follow these steps to configure a fault state delay.

1.

On the Module Properties dialog box, click the Output State tab.

2.

Complete the fields as described in the table below and click OK.

Field

Description

1756-OB16IEF
Configuration Tag

1756-OB16IEFS
Configuration Tag

Fault Mode Output State
Duration

Choose the length of time you want the output to remain in Fault mode state
before transitioning to the final state:
1 second
2 seconds
5 seconds
10 seconds
Forever (default)
IMPORTANT: If you choose Forever, the output will remain in the Fault mode
state until a connection is reestablished. For example, if the Fault mode is Hold,
and you specify a duration of Forever, then the output retains its Hold state and
does not transition to a Final state if a fault occurs.

Pt[x].FaultValueStateDuration

FaultValueStateDuration

Fault Mode Output State
Final State

Choose whether you want the module to transition to an On or Off state after the
Fault mode duration time elapses.
The default final state is Off. If you chose Forever, you cannot choose a final state.
The module will retain its current Fault mode state.

Pt[x].FaultFinalState