Linking Device Function Blocks Chapter 7

10

MANUFAC_ID

Unsigned32

Enumeration;
controlled by FF

0x00014D None

RO

Manufacturer identification number - used by an
interface device to locate the DD file for the resource
block.

11

DEV_TYPE

Unsigned16

Set by mfgr

None

RO

Manufacturer model number associated with the
resource block - used by interface devices to locate the
DD file for the resource block.

12

DEV_REV

Unsigned8

Set by mfgr

None

RO

Manufacturer revision number associated with the
resource block - used by an interface device to locate
the DD file for the resource block.

13

DD_REV

Unsigned8

Set by mfgr

None

RO

Revision of the DD associated with the resource block -
used by an interface device to locate the DD file for the
resource block.

14

GRANT_DENY

DS-70

0

N/A

RW

Not user configurable.

15

HARD_TYPES

Bitstring(2)

Set by mfgr

N/A

RO

Not user configurable.

16

RESTART

Unsigned8

1: Run,
2: Resource,
3: Defaults,
4: Processor
5: Factory

0

E

A

Allows a manual restart to be initiated. Several
degrees of restart are possible.

17

FEATURES

Bitstring(2)

Set by mfgr

N/A

RO

Used to show supported resource block options. See
FEATURES Bits on

page 110

.

18

FEATURE_SEL

Bitstring(2)

See
FEATURE_SEL
Bits on page 111

0

N/A

A

Used to select resource block options.

19

CYCLE_TYPE

Bitstring(2)

Set by mfgr

N/A

RO

Identifies the block execution methods available for
this resource block. This parameter is reserved for
future use. See CYCLE_TYPE Bits on

page 110

.

20

CYCLE_SEL

Bitstring(2)

See CYCLE_SEL
Bits on page 111

0

N/A

A

Used to select the block execution method for this
resource block. This parameter is reserved for future
use.

21

MIN_CYCLE_T

Unsigned32

Set by mfgr

0

1/32 ms

RO

Time duration of the shortest cycle interval of which
the resource block is capable.

22

MEMORY_SIZE

Unsigned16

Set by mfgr

kB

RO

Available configuration memory in the empty resource.
To be checked before attempting a download. This
parameter is reserved for future use.

23

NV_CYCLE_T

Unsigned32

0

1/32 ms

RO

Interval between writing copies of NV parameters to
nonvolatile memory. Zero means never.

24

FREE_SPACE

Float

0 to 100%

%

RO

Percent of memory available for further configuration.
Zero in a preconfigured resource. This parameter is
reserved for future use.

25

FREE_TIME

Float

0 to 100%

%

RO

Percent of the block processing time that is free to
process additional blocks. This parameter is reserved
for future use.

26

SHED_RCAS

Unsigned32

640000

1/32 ms

AUTO

Not user configurable.

27

SHED_ROUT

Unsigned32

640000

1/32 ms

AUTO

Not user configurable.

28

FAULT_STATE

Unsigned8

0: Uninitialized
1: Clear
2: Active

0

E

RO

Condition set by loss of communication to an output
block, failure promoted to an output block or a physical
contact. When Fault State condition is set, then output
function blocks will perform their FSAFE actions.

Table 5 - RES Block Parameters

Index

Parameter

Data Type
(length)

Valid Range/
Options

Default
Value

Units

Edit
Mode

Description