Advanced Diagnostics and Hidden Web Pages Chapter 10

H1 Captures

An H1 capture is in 256 KB blocks and the file size increases by 256 KB. The H1
capture saves the data of all four ports.

Follow these steps to capture information about fieldbus communication on a
linking device H1 port.

1.

On the Capture page, verify that H1 is selected (default) as the Capture
Type.

2.

Click Browse.

The H1 Capture File Location dialog box appears.

3.

Browse to an existing folder or create a new folder.

4.

Type a File name and click OK.

The H1 File Location field is populated.