Rockwell Automation 1757-FFLDC4 FOUNDATION Fieldbus System User Manual User Manual

Page 92

Advertising
background image

92

Rockwell Automation Publication 1757-UM012A-EN-P - July 2011

Chapter 5 Create an RSLogix 5000 Software Project

3.

Review the checkboxes on this dialog box.

4.

Click OK.

Field

Description

Requested Packet Interval (RPI)

Choose the RPI to determine the rate at
which a communication module, such as a
1756-ENBT module, queries the block.

Inhibit Module

Check the box to prevent communication
between the owner-controller and the
module. This option allows for maintenance
of the module without faults being reported
to the controller.

See Module Inhibiting in the ControlLogix
Analog I/O Modules User Manual,
publication

1756-UM009

, for more

information.

Major Fault On Controller If Connection Fails
While in Run Mode

Check the box to create a major fault if there
is a connection failure with the module while
in Run mode.
For important information on this checkbox,
see ‘Configure a Major Fault to Occur’ in the
Logix5000 Controllers Information and
Status Programming Manual,
publication

1756-PM015

.

Use Unicast Connection on EtherNet/IP

Displays only for analog modules using
RSLogix 5000 software version 18 or later in
a remote EtherNet/IP chassis.
Use the default checkbox if there are no
other controllers in ’Listen’ mode and data is
to be sent to a specific owner-controller.

Clear the box if there are other ’listening’
controllers in the system.

Module Fault

If a fault occurs, its details appear in this
section of the tab.

IMPORTANT

Adding Logix Blocks online in RSLogix 5000 software with ‘Major
Fault on Controller If Connection Fails While in Run Mode’
checked may result in faulting the controller if the Logix Block has
not been already downloaded via RSFieldbus software or the
Logix Block is configured to use a scheduled connection.