Linking Device Function Blocks Chapter 7

8–15

Reserved

CYCLE_SEL Bits

0

Scheduled

1

Block Execution

2

Manufacturer Specific

3–15

Reserved

CYCLE_TYPE Bits

0

Scheduled (LSB)

1

Completion of block execution

2

Manufacturer specific

3–15

Reserved

FEATURES Bits

0

Reserved

1

Not used

2

Fault State supported
If this feature is selected in FEATURE_SEL, setting the SET_FSTATE parameter will
force all output function blocks (AO and DO) in the resource to go to fault state.
Individual output function block will go to Fault State due to a loss of communication
to CAS_IN or IFS status in CAS_IN, regardless the selection of this feature.

3

Soft Write lock supported
Select this feature to enable the WRITE_LOCK parameter.

4–7

Reserved

8

Change of bypass in an automatic mode

(1)

If this feature is selected in FEATURE_SEL, it is allowed to write in BYPASS in an
automatic mode, otherwise only in Man or OOS modes.

9–15

Reserved

FEATURE_SEL Bits

0

Not used

1

Fault State Supported
If this feature is selected in FEATURE_SEL, setting the SET_FSTATE parameter will
force all output function blocks (AO and DO) in the resource to go to fault state.
Individual output function block will go to Fault State due to a loss of communication
to CAS_IN or IFS status in CAS_IN, regardless the selection of this feature.

2

Soft Write Lock Supported
Select this feature to enable the WRITE_LOCK parameter.

3

Change of Bypass in an Automatic Mode
If this feature is selected in FEATURE_SEL, it is allowed to write in BYPASS in an
automatic mode, otherwise only in Man or OOS modes.

4–15

Reserved

(1) This characteristic depends on the hardware type.

Table 6 - Block Options