A - troubleshoot the linking device, Introduction, 1757-ffld status indicators – Rockwell Automation 1757-FFLDC4 FOUNDATION Fieldbus System User Manual User Manual

Page 145: Appendix a, Troubleshoot the linking device, Introduction 1757-ffld status indicators, Appendix

Advertising
background image

Rockwell Automation Publication 1757-UM012A-EN-P - July 2011

145

Appendix

A

Troubleshoot the Linking Device

Introduction

This appendix describes options for troubleshooting the 1757-FFLD

x and the

1757-FFLDC

x linking devices.

The table describes the topics in this section.

1757-FFLD
Status Indicators

The table provides a description of the status indicators to evaluate the
performance of the 1757-FFLD linking device.

Topic

Page

1757-FFLD Status Indicators

145

1757-FFLDC Status Indicators

146

ControlNet Network Status Indicators

147

Reset the Linking Device

149

Table 12 - 1757-FFLD Status Indicators

Indicator

Status

Description

H1

Off

The H1 channel is inactive.
Verify that the linking device is connected to the
H1 network.

Flashing green

The linking device H1 channel is active.

STATUS
(module)

Off

No power - Module does not have 24V DC power.

Flashing green

Standby - Module is not configured or a duplicate IP
address is detected.
Configure the module. Assign a new IP address.

Solid green

Operational - Module is operating correctly.

Flashing red

Minor fault - A recoverable fault has been detected.
Verify that the configuration is correct and
consistent.

Solid red

Major fault - An unrecoverable fault has been
detected.
Recycle power to the module. If this does not clear
the fault, replace the module.

WDOG
(\watchdog)

Off

Normal operation.

Flashing red

Software fault.
Contact Rockwell Automation Technical Support at

http://www.rockwellautomation.com/support/

.

BATT
(battery)

Off

Normal operation.

Flashing red

Jumper is missing (or not seated on the two
rightmost pins), or the battery is low or dead

(1)