Rockwell Automation Publication 1757-UM012A-EN-P - July 2011

69

RSFieldbus Communication Chapter 4

There is an order of precedence in associating devices. The bridges on the
HSE network need to be associated prior to the devices on the H1
network, because the linking device is the link between the H1 and the
host computer.

3.

Right-click the linking device and choose Attributes.

The Bridge dialog box appears.

4.

From the Device Id pull-down menu, choose the corresponding device ID.

5.

Click OK.

Note that the red ‘x’ in the HSE window has disappeared once the
association is made. This indicates that communication with the linking
device is established.

The next step requires opening the Live List to verify that you are
connected to the proper devices.

6.

Right-click H1-1 network and choose Live List.

The H1-1 Live List appears and shows all of the devices connected
through your linking device.