1757-ffldc status indicators – Rockwell Automation 1757-FFLDC4 FOUNDATION Fieldbus System User Manual User Manual

Page 146

Advertising
background image

146

Rockwell Automation Publication 1757-UM012A-EN-P - July 2011

Appendix A Troubleshoot the Linking Device

1757-FFLDC
Status Indicators

The table provides a description of the status indicators to evaluate the
performance of the 1757-FFLDC linking device.

NS
(network status)

Off

Not powered.

Flashing green

No connections.
Verify that the linking device is connected to the
fieldbus network.

Solid green

CIP connections.

Flashing red

Connection timeout.
Verify the linking device is connected to the Ethernet
network.

Flashing red and
green

Self-test.

MODE

Solid green

Linking device is operational.

Flashing green

Linking device is out-of-service. Duplicate IP address
detected.
Verify that the Resource block is set to Target Auto
mode. Assign a new IP address.

(1) If the BATT status indicator remaions on after the jumper is replaced, and power has been returned to the

linking device, contact Rockwell Automation Technical Support.

Table 12 - 1757-FFLD Status Indicators

Indicator

Status

Description

Table 13 - 1757-FFLDC Status Indicators

Indicator

Status

Description

H1

Off

The H1 channel is inactive.
Verify that the linking device is connected to the
H1 network.

Flashing green

The linking device H1 channel is active.

STATUS
(module)

Off

No power - Module does not have 24V DC power.

Flashing green

Standby - Module is not configured.

Solid green

Operational - Module is operating correctly.

Flashing red

Minor fault - A recoverable fault has been detected.
Verify that the configuration is correct and
consistent.

Solid red

Major fault - An unrecoverable fault has been
detected.
Recycle power to the module. If this does not clear
the fault, replace the module.

WDOG
(\watchdog)

Off

Normal operation.

Flashing red

Software fault.
Contact Rockwell Automation Technical Support at

http://www.rockwellautomation.com/support/

.

BATT
(battery)

Off

Normal operation.

Flashing red

Jumper is missing (or not seated on the two
rightmost pins), or the battery is low or dead

(1)