Appendix D Connections

Table 26

shows an example of counting your ControlNet network connections.

To determine the number of connections and packets per second for an Ethernet
network, use the EtherNet/IP Capacity tool at

http://www.ab.com/go/iatools

.

In Example 1, if a 1756-CNB ControlNet bridge module is being used, the
network could be considered fully loaded because this module supports 64
connections.

In Example 2, if a 1756-CNB ControlNet bridge module is being used, the
network could be considered fully loaded and even too close to the connection
limit. We recommend that you have a number of spare connections for additional
connections that may occur.

Table 26 - ControlNet Network Examples

Example 1

Example 2

Number of 1757-FFLDC linking devices

3

10

Number of Logix Blocks used per
linking device

16

4

Class 1 connections
(1 per Logix Block)

48

40

Class 3 connections
(2 per linking device)

6

20

Controller connection to the ControlNet bridge or
interface module

1

1

Total connections

55

61