Chapter 3

Create an RSFieldbus Software Project

Set the Stale Count

Stale count is the number of macrocycles that elapse before a signal is sent to
indicate there has been no update of the link data.

Do these steps to change the stale count.

1.

In the Process Cell window, right-click the control module icon and
choose Attributes.

The Control Module dialog box appears.

2.

Enter a stale count value and click OK.

The Control Module is added to your configuration.

Table 1 - Stale Count Examples

Macrocyle

Stale Count

Delay Before a Link Failure is Indicated via the Input
Fault Bit or Quality/Status Data

200 ms

10

2 s

1000 ms

10

(1)

(1) A more appropriate stale count for this example may be 3 or 4 seconds depending on the

application requirements.

10 s