37

Create an RSFieldbus Software Project Chapter 3

2.

Configure the device by entering information in the New Device
dialog box.

3.

Repeat steps

1

and

2

for additional devices.

4.

Click the Advanced Options tab.

Use the default of ‘Creation based on Default Template’.

5.

Click OK.

Field

Description

Manufacturer

Choose a manufacturer from the
pull-down menu.

Device Type

Choose a device type from the
pull-down menu.

Device Rev

Choose the device revision.
IMPORTANT: The DD and CF values default
to the latest revisions in the device support
files if the ‘Follow the Latest DD and CF
Revisions’ box is checked.

If the DD and CF revisions do not match your
device firmware, clear the box and choose
the correct revisions.

Capability Lev

Defaults to the capability of the instrument.

Device Tag

Type a Device Tag. If you do not enter a tag,
the default tag is Device_#.

IMPORTANT

If the correct revisions are not listed, the correct DDs need to be
imported. Refer to Device Support in the appendix.

If you do not match the correct revisions with your device
firmware, you receive a warning on download. Incorrect DD files
will cause download failures, which results in the project
configuration not functioning for that device.