Rockwell Automation 1757-FFLDC4 FOUNDATION Fieldbus System User Manual User Manual

Page 148

Advertising
background image

148

Rockwell Automation Publication 1757-UM012A-EN-P - July 2011

Appendix A Troubleshoot the Linking Device

The table provides a description of the status indicators for channels on the
ControlNet network that are used along with the 1757-FFLDC linking device.

Alternating red/
green

Self-test

None.

Incorrect channel
configuration

Verify that the ControlNet network is connected to
the correct channel of the linking device (for
example), if the ControlNet network is configured for
channel A only, then the linking device must be
connected to the network via channel A).

Alternating red/off

Duplicate ControlNet
node address

Choose a unique node address.
Cycle power to the linking device.

Table 15 - ControlNet Channel Troubleshooting (A AND B)

AND Cause

Action

Off

Channel disabled.

Use RSNetwork for ControlNet software to
configure the ControlNet network for redundant
media, if required.

Solid green

Normal operation

None.

Flashing green/off

Temporary network
errors

Check media for broken cables, loose connectors,

or missing terminators.

If condition persists, refer to the ControlNet

Media Planning and Installation Manual,
publication

CNET-IN002

.

Flashing red/off

Media fault

Check media for broken cables, loose connectors,

or missing terminators.

If condition persists, refer to the ControlNet

Media Planning and Installation Manual,
publication

CNET-IN002

.

No other nodes
present on network

Add other nodes to the network.

Flashing red/green

Incorrect ControlNet
node address

Change linking device node address so that it is

less than or equal to UMAX.

(1)

Cycle power to the linking device.

(1) UMAX is the highest node address on a ControlNet network than can transmit data.

Incorrect network
configuration

Use RSNetWorx for ControlNet software to
reconfigure the ControlNet network so that UMAX

(1)

is greater than or equal to the linking device’s
node address.

Table 14 - ControlNet Network Troubleshooting (A AND B)