Advanced Diagnostics and Hidden Web Pages Chapter 10

Reset the Linking Device

The linking device can be reset in the following ways. Shaded cells indicate the
reset types described in this chapter.

IMPORTANT

When you reset the linking device, it no longer communicates with other
fieldbus devices. Make sure your process is shut down or under manual
control before you reset the linking device.

Reset Type

Description

How

Information Is Found

Reset device

This restarts the linking device but does not change any
configuration.

Web page reset (remotely)

Following procedures

Reset
configuration

This restarts the linking device and deletes all downloaded
fieldbus configurations. The linking device retains its network
configuration and web page password information through
this reset.

Reset jumper (locally)

See

page 149.

Web page reset (remotely)

Following procedures

RSLogix 5000 reset (remotely)

See

page 152

Reset to factory
defaults

This resets the web page user name and password, resets all
services (for example, web services), and clears all
downloaded fieldbus configuration.

Reset button (locally)

See

page 149.

Web page reset (remotely)

Following procedures

Reset function
block
parameters

This resets all block parameters to default. All blocks in the
linking device are retained, including tag names and
macrocycle timing.

RSFieldbus Resource Block,
Default parameter (remotely)

See

page 151.

Reset/delete
function blocks

This deletes all blocks in the linking device except for the
Resource Block. All Resource Block parameters are reset to
factory default, including the tag name.

RSFieldbus Resource Block,
Factory parameter (remotely)

See

page 151.

IMPORTANT

After you complete any type of reset, verify that the time and time zone
still are correct.