Publication 2706-UM016D-EN-P - March 2006

InView Protocol 4-37

Transmission:

Transmission for Updating Variable Registers with 10 Frame Broadcast

Response: NONE

Update Variables using a Modbus ASCII 10 frame in Guaranteed
mode

This method allows the ability to update more than one variable in a
specific display address. A maximum of 60 registers can be updated in
one transmission. Unused high order bits must be set to zero. The
following is an example of updating variables 1, 2, and 3 with values
23, 734, and 7 respectively in display address 003.

Below is an example of a preset multiple register transmission.

Transmission:

Query for Updating Variable Registers using a 10 Frame

Beginning of
Frame

ADDR

FUNC

H.O.
ADDR

L.O.
ADDR

QUANTITY

BYTE CNT

DATA

:

FF

10

00

00

0003

06

0018 0035

0038

LRC
Error

EOF

Ready to rec. resp

63

CR

LF

Beginning
of Frame

ADDR

FUNC

H.O.

ADDR

L.O.

ADDR

QUANTITY

BYTE CNT

DATA

:

03

10

00

00

0003

06

0017 02DE

0007

LRC

Error

EOF

Ready
to rec.
resp

E6

CR

LF