Publication 2706-UM016D-EN-P - March 2006

Install InView Marquee Message Display 1-21

7. Insert the wires into the appropriate terminal connection and

tighten the screw to 0.79 Nm (7 lb-in).

The terminal block is UL rated for wire ranges of 14 to 8 AWG.

8. Remove the necessary hole plugs before connecting the

communications cables.

9. Connect the incoming communication wires per the tables

below.

TB1 is used for P9x pass-through. TB2 is used for supplying
power to the optional InView Legacy Communication board kit.

ATTENTION

Use shielded Ethernet cable. Shielded Ethernet
cable is required to maintain noise immunity.

The 2706-PCable1 is used for downloading
messages only and must be removed after
downloading is complete.

Power connection

LINE 1

GR
OUND

LINE 2 OR

NEUTRAL

LINE 1

GR
OUND

LINE 2 OR

NEUTRAL

208 - 240 VAC INPUT

Neutral
(Line 2): WHITE

Line
(Hot) BLACK

Ground
GREEN w/ Yellow

RJ-12

TB3

TB2

TB1

Ethernet

Communication
Openings

TB1 RS-485

Pin

Pin Name

Pin

Pin Name

1.

GND

4.

CH A

2.

SHLD

5.

CH B

3.

COMM

6.

TERM