InView Protocol 4-51
Set Serial Address
This command will change a serial address for a display.
Text Position Placement
Allen-Bradley uses the 2706-P42, 2706-P44, and 2706-P72 series
displays with InView industrial protocol. The displays can be single
line, two-line or 3-line. Displaying of messages using protocol is
slightly different based on which display is being used.
Below are some rules for the 2706-P44 and 2706-P72 display. The
2706-P42 display ignores the display position and show (display) the
text.
Special Function Command to Set Serial Address
<SOH>
Type Code
Display Address
Description
ASCII
Hex
Description
ASCII
Hex
Description
ASCII
Hex
Start of Header
^A
01
All displays
Z
5A
Display Address
01-FF
3031-4646
Special Function Command to Set Serial Address Continued
<STX>
Command Code
Command
Function
Description
ASCII
Hex
Description
ASCII
Hex
Description
ASCII
Hex
Start of Text
^B
02
Write Special Function
E
45
Set address
7
37
Special Function Command to Set Serial Address Continued
Command Code (Continued)
<EOT>
Serial address
ASCII
Hex
Description
ASCII
Hex
New serial address
01-FE
3031-4645
End of Transmission
^D
04