Publication 2706-UM016D-EN-P - March 2006

Install InView Marquee Message Display 1-15

2. Feed electrical cable through 2.54 cm (1 in.) water-tight conduit,

the outside end of the connector (supplied), the electrical
opening in the sign case, and then through the inside end of the
connector.

3. Screw the inside and outside ends of the connector together

until water-tight.

4. Strip the electrical wires back 6.35 cm (0.25 in.).

5. Connect the wires by screwing the end of each wire into the

power connection.

6. If the sign is to be used with serial communications, remove one

or both of the hole plugs from the lowest holes on the right end
of the sign case.

Otherwise, proceed to Step 7.

Right-end
view

Electrical opening

Front view

Sign case,
inside

Conduit

Connector,
outside end

Connector nut, with teeth
facing the sign case

Rubber gasket

Power connection

LINE 1

GR
OUND

LINE 2 OR

NEUTRAL

LINE 1

GR
OUND

LINE 2 OR

NEUTRAL

208 - 240 VAC INPUT

Neutral
(Line 2):
WHITE

Line
(Hot)
BLACK

Ground
GREEN
w/
Yellow

Serial device hole
plug/opening

Right-end view

TIP

TB1 can be used for incoming serial connection for
RS-232 or RS-485. The full pinout diagram is shown
below.