Wiring recommendations, European union directive compliance – Rockwell Automation 2706-F11J_F11JC_F21J_F21JC DL50 INSTALLATION MANUAL User Manual

Page 34

Advertising
background image

Chapter 4

Installing the DL50

4–9

Careful wire routing helps cut down on electrical noise. To reduce electrical
noise, the DL50 should be connected to its own branch circuit. (See the next
section for power requirements in the European Union or EFTA regions.)The
input power source should be protected by a fuse or circuit breaker rated at
no more than 15 Amps. Route incoming power to the DL50 by a separate
path from the communication cables.

!

ATTENTION: Do not run signal wiring and power wiring in
the same conduit!

Where power and communications lines must cross, they should cross at
right angles. Communications lines can be installed in the same conduit as
low level DC I/O lines (less than 10 Volts).

All communications lines should be shielded. The shield should be connected
to ground only at the transmitting device.

If this product is installed within the European Union or EFTA regions, the
following regulations apply:

EMC Directive

This apparatus is tested to meet Council Directive
89/336/ECElectromagnetic Compatibility (EMC) using the following
standards

:

EN 50081-2
EMC – Generic Emission Standard, Part 2 Industrial Environment

EN 50082-2
EMC – Generic Immunity Standard, Part 2, Industrial Environment

.

LVD Directive

This apparatus is tested to meet Council Directive 73/23/EEC with
amendments, including 93/68/EEC Low Voltage (LVD) using the following
standard:

EN 60950 Safety of Information Technology Equipment

.

Intended Use of Product

The products described in this manual are intended for use in an industrial
environment as defined in Appendix H.

Wiring Recommendations

European Union Directive
Compliance

Advertising