Plc-5 channel 0 simplex example – Rockwell Automation 2706-F11J_F11JC_F21J_F21JC DL50 INSTALLATION MANUAL User Manual

Page 82

Advertising
background image

Chapter 6

Slave Mode Operation / Examples

6–18

PLC-5 Channel 0 Simplex Example

This example demonstrates how to use the RS232 Channel 0 of supporting
members of the Allen-Bradley PLC-5 family to trigger a Dataliner DL50
display. In the example, a counter is used to simulate changing variable data,
which could be a motor speed or a temperature. This will demonstrate how
variable data may be incorporated into messages.

The program below will display the message “Temp ##” in green (red on
F11J or F21J), where ## represents the sample variable. The text size will
depend on the character size setting on the DL50 display.

Temp ##

Channel 0 Configuration

The first step is to configure the PLC channel 0 port to communicate with a
DL50 slave. Table 6.C shows the user mode configuration of the PLC
channel 0. Note that the baud rate should match that being used by the DL50.

Table 6.C
Configuring the Channel 0 Port

Channel 0

Channel 1A
Channel 1B
Channel 2A
Channel 2B

Channel 3A

DH+

SCANNER MODE

USER

ADAPTER MODE

N/A

SCANNER MODE

User Mode

Channel 0 Configuration

Diag.file:

Remote mode change:
Mode Attention Char.:

Baud rate:
Stop bits:

Control line:

Echo/delete mode:

Termination 1:

Termination 2:

N11

DISABLED

\0x1b

9600

1

NO HANDSHAKING

CRT

\0xd

\0x0

XON/XOFF:

DISABLED

System mode char.:

S

User mode char.:

U

Parity:

NONE

Bits per character:

8

RTS send delay (20 ms):

0

RTS off delay (20 ms):
Append 1:

\0xd

0

Append 2:

0