Chapter 4

Installing the DL50

4–15

Figure 4.12

shows a typical connection between a host device RSĆ485 port and

DL50 displays. We recommend that you use Belden 9842 cable.

Note that pin or terminal numbers are not shown for the host device. This is
because the terminal numbers vary for different products. For actual pin
numbers, refer to the appropriate host device product literature.

We recommend that you connect the shield to ground at one end only, as
shown.

Figure 4.12
RS-485 Connections

Note: Some devices require that certain
hardware handshaking lines be asserted.

Refer to the applicable product literature.

RS-485 (+)

RS-485 (-)

To

Other
DL50s

DL50

RS-485

TERMINALS

+

SHLD

COM

Common

Shield

1

6

2

3

4

5

+

SHLD

COM

+

SHLD

COM

1

2

3

4

5

6

+

SHLD

COM

E. GND

TERM

HOST

TERMINALS

DL50

RS-485

TERMINALS

DL50

RS-485

TERMINALS

2

3

4

5

2

3

4

5

Connect shield (terminal #2) to ground
(terminal #1) at any one node (only) on
RS-485 Network

1

2

3

4

5

6

+

SHLD

COM

E. GND

TERM

Terminate the network at the last device.
Terminate a DL50 by connecting RS-485 +
(terminal #4) to
TERM (terminal #6).

Shield

Grounding

Network

Termination

BLACK BOX

LD485A-MP

DL50 DISPLAY

DL50 DISPLAY

To Other DL50 Displays

Note: RS-232 devices such as
personal computers can communi-
cate through the DL50 RS-485
port using an RS-232

! RS-485

converter such as a Black Box

TM

LD-485A-MP.

1

6

1

6

RS-232

RS-485

RS-232

RS-485

Advertising