Chapter 5

Serial Communications

5–13

Field 6: Message Attributes

(continued)

Third Byte Message Attributes- The third byte of the Message Attributes
field is reserved for future enhancements. Always set the eighth bit to 1 so
that the field is not misinterpreted as a control character:

Bit

7

Bit

6

Bit

5

Bit

4

Bit

3

Bit

2

Bit

1

Bit

0

Always Set
To 1

Reserved

Field 7: Checksum

This is a three byte field that contains:

Checksum

Dummy Byte

Byte 1

1 Byte

Checksum MSB

Byte 2

1 Byte

Byte 3

1 Byte

Checksum LSB

If either the Checksum Most Significant Byte (MSB) or Checksum Least
Significant Byte (LSB) contain a value equivalent to a CR (decimal 13), the
content of the dummy byte is adjusted to alter the value of the Checksum
bytes. Refer to Appendix F for a description of how the checksum bytes
are calculated.

Important: To disable the checksum, set the DL50 DIP switch S2 position 8
to Off (refer to Figure 3.2). With the checksum disabled, your host duplex
messages must still contain 3 bytes in Field 7, but the checksum value is
ignored by the DL50.