Chapter 4

Installing the DL50

4–25

Use the Flexible Interface Module with either the Catalog No. 2760-SFC1 or
2760-SFC2 cartridge with Dumb Terminal (DT) protocol. Multidrop up to 31
DL50’s on each of the three communications ports on the module.

Figure 4.21 shows how to connect the RS-485 port of the DL50 to a Flexible
Interface Module RS-422 port.

Figure 4.21
RS-485 Connection to a Flexible Interface Module

To

Other

DL50s

1

2

4

5

6

1

+

SHLD

+

SHLD

DL50

RS-485

TERMINALS

DL50

RS-485

TERMINALS

2

4

5

6

FLEXIBLE

INTERFACE

MODULE

(RS-422)

3

COM

COM

3

Shield

Common

RS-485 (+)

1

+

SHLD

DL50

RS-485

TERMINALS

2

4

5

6

COM

3

RS-485 (–)

Flexible Interface Module

Network Termination

Terminate RS-422 network at
Flexible Interface Module.
Refer to User Manual.

Shield

Grounding

Connect shield (terminal #2) to
ground (terminal #1) at any one node
(only) on RS-422 Network.

Network

Termination

Terminate last DL50 by connecting
RS-422 + (terminal #4) to
TERM (terminal #6)

1

+

SHLD

2

4

5

6

COM

3

TERM

E. GND

1

+

SHLD

2

4

5

6

COM

3

TERM

E. GND

Flexible Interface Module
Catalog No. 2760-RB