The RS-485 interface has these advantages over the RS-232

:

Improved noise immunity.

DL50 displays can be a distance of up to 4000 feet (1200 m) from the
host device.

Up to 32 devices can be connected directly to the RS-485 port of the host
controller. Up to 100 DL50 displays can be addressed when line drivers
are used.

Figure 4.11 shows the location of the DL50’s RS-485 port terminals. The
terminals are labeled:

RS-485 Connection Terminals

Label

Function

Definition

1

E. GND

Earth Ground

2

SHLD

Shield

3

COM

Common

4

+

RS-485 + (B)

5

-

RS-485 - (A)

6

TERM

Termination

Figure 4.11
RS-485 Terminal Location

RESET

RESET

SHLD (Terminal #2)

COM (Terminal #3)
+ (Terminal #4)

- (Terminal #5)

TERM (Terminal #6)

E. GND (Terminal #1)

RS-485 Connections