Chapter 4

Installing the DL50

4–20

Figure 4.17
Personal Computer to DL50 RS-485 Port(s)

Signal Ground

Receive

Transmit

5

3

2

Computer
RS-232 port

DB-9 Connector

1

2

3

4

5

6

+

SHLD

COM

DL50

RS-485

TERMINALS

2
3
7

NOTE: CONNECT SHIELD TO EGND AT
ONE NODE ONLY

TERM

RxB

RxA

TxB

TxA

RS-485

Shield

DB-25

RS-232

Black Box LD485A-MP

Note: Allen-Bradley 2706-NC15 cable will
connect directly from a personal computer
serial port (male DB-9) to the Black Box
LD485A-MP.

EGND

Black Box LD485A-MP Configuration

Configure the Black Box (LD485A-MP) converter as follows:

1. Remove cover and set the converter as a DCE device using the XW1A

jumper. This is a 16-pin DIP jumper.

2. Short TxA and RxA on TB1 of the converter.

3. Short TxB and RxB on TB1 of the converter.

4. Set jumper W8 to half-duplex operation.

5. Set jumper W9 for a 50 millisecond RTS/CTS delay time.

6. Set jumper W15 to B-C for data enabled operation.

7. Set jumper W16 to A-B for 5 millisecond turnaround delay.

8. Set jumper W17 to A for 1 millisecond driver delay.

9. Set jumper W18 to A-B for DTR enabled driver.

10.Set switch S2 to the unterminated position.

11. Replace cover.

12.Set Normal/Loopback switch on front panel to Normal.

!

ATTENTION: The two jumpers to short TxA to RxA and TxB
to RxB are essential for converter function. See steps 2 and 3
above, and Figure 4.17.