Complying with european union directives, Emc directive, Meeting ce requirements – Rockwell Automation 8720MC High Performance Drives Installation Manual User Manual

Page 14: Complying with european union directives -2, Emc directive -2 meeting ce requirements -2

Advertising
background image

Publication 8720MC-IN001D-EN-P — December 2002

1-2

Installing Your 8720MC Drive

Complying with European
Union Directives

If this product is installed within the European Union or EEC regions
and has the CE mark, the following regulations apply.

For more information on the concept of electrical noise reduction,
refer to System Design for Control of Electrical Noise (publication
GMC-RM001x-EN-P).

EMC Directive

This unit is tested to meet Council Directive 89/336/EEC
Electromagnetic Compatibility (EMC) using the following standards, in
whole or in part:

• EN 50081-2 EMC — Generic Emission Standard,

Part 2 — Industrial Environment

• EN 50082-2 EMC — Generic Immunity Standard,

Part 2 — Industrial Environment

The product described in this manual is intended for use in an
industrial environment.

Meeting CE Requirements

To meet CE requirements the following components are required:

• Install an AC line filter as close as possible to the module (8720MC

drive or 8720MC-RPS) where three-phase input power connects.
Refer to Appendix C for available AC line filter catalog numbers.

• Use 2090 series motor power cables (MP-Series motors) or use

connector kits. Clamp the cable shields at the drive and provide a
ground path to the motor ground terminal on TB1. Refer to
Chapter 3 for wiring examples and guidelines when making your
own 8720SM cables.

• Use 2090 series motor feedback cables (MP-Series and 8720SM S1,

S2, and S4 motors) or use connector kits. Terminate the feedback
shield to the chassis clamp provided. Refer to Chapter 3 for wiring
examples and guidelines when making your own 8720SM cables.

• Install the 8720MC system inside an enclosure. Run input power

wiring (clamped to the enclosure) in conduit outside of the
enclosure. Separate signal and power cables as shown in
Planning Your Panel Layout beginning on page 1-14.

• Motor power/feedback cable length must not exceed 90 m (295.2

ft). Refer to Appendix C for motor connector kit catalog numbers.