Publication 8720MC-IN001D-EN-P — December 2002

Connecting Your 8720MC

3-7

Using Lug Connectors

The D frame has stud type terminals, which require using lug
connectors for cable terminations. The following table shows the lug
selection for each possible cable choice. Choose connectors for each
installation based on the desired cable sizes, the application
requirements, and all applicable national, state, and local codes.

Lug Selection

1

5/16 inch stud. All other studs are 3/8 inch.

Drive Catalog
Number

Output U, V, W and PE

DC+
DC-

TE

Cable (per Phase)
mm

2

(AWG)

T & B Part No.
(8 required)

Cable (per Phase)
mm

2

(AWG)

T & B Part No.
(2 required)

Cable (per Phase)
mm

2

(AWG)

T & B Part No.
Number

8720MC-D097

33.6 (2)

54147

1

21.2 (4)

54139

1

13.3 (6)

54135

1

8720MC-D120

53.5 (1/0)

54153

1

33.6 (3), (2)

54142

1

13.3 (6)

54135

1

8720MC-D149

85.0 (3/0)

54163

1

53.5 (1/0)

54153

1

13.3 (6)

54135

1

8720MC-D180

107.2 (4/0)

54168

1

67.4 (2/0)

54110

1

21.2 (4)

54139

1

Advertising