Using lug connectors, Lug selection, Using lug connectors -7 – Rockwell Automation 8720MC High Performance Drives Installation Manual User Manual
Page 69: Lug selection -7

Publication 8720MC-IN001D-EN-P — December 2002
Connecting Your 8720MC
3-7
Using Lug Connectors
The D frame has stud type terminals, which require using lug
connectors for cable terminations. The following table shows the lug
selection for each possible cable choice. Choose connectors for each
installation based on the desired cable sizes, the application
requirements, and all applicable national, state, and local codes.
Lug Selection
1
5/16 inch stud. All other studs are 3/8 inch.
Drive Catalog
Number
Output U, V, W and PE
DC+
DC-
TE
Cable (per Phase)
mm
2
(AWG)
T & B Part No.
(8 required)
Cable (per Phase)
mm
2
(AWG)
T & B Part No.
(2 required)
Cable (per Phase)
mm
2
(AWG)
T & B Part No.
Number
8720MC-D097
33.6 (2)
54147
1
21.2 (4)
54139
1
13.3 (6)
54135
1
8720MC-D120
53.5 (1/0)
54153
1
33.6 (3), (2)
54142
1
13.3 (6)
54135
1
8720MC-D149
85.0 (3/0)
54163
1
53.5 (1/0)
54153
1
13.3 (6)
54135
1
8720MC-D180
107.2 (4/0)
54168
1
67.4 (2/0)
54110
1
21.2 (4)
54139