Publication 8720MC-IN001D-EN-P — December 2002

3-24

Connecting Your 8720MC

Connecting to the External
Active Shunt Module

These procedures assume your configuration requires additional shunt
capacity, your external active shunt module is mounted to the panel,
and you are ready to wire the shunt module.

Use the 1336-MOD-KBxxx active shunt with your 8720MC AC drive
(refer to Appendix C for catalog numbers).

Refer to Appendix B for the 8720MC interconnect diagrams.

To wire your shunt module:

1. Route the DC bus power wires (DC+, DC-) to TB1 on the drive

from your external shunt module.

2.

3. Tighten the connections.

4. Gently pull on each wire to make sure it does not come out of its

terminal. Re-insert and tighten any loose wires.

5. Go to Understanding Feedback and I/O Cables.

IMPORTANT

When tightening screws to secure the wires, refer to
the table on page 3-15 for torque values.

IMPORTANT

To ensure system performance, run wires and cables
in the wireways as established in Chapter 1.

Insert this wire from
the shunt module:

Into this terminal
on the drive:

TB1-DC+

TB1-DC+

TB1-DC-

TB1-DC-

TB3-1

115V ac

TB3-2

TB3-3

P5-22

TB3-4

P5-36