Publication 8720MC-IN001D-EN-P — December 2002

3-4

Connecting Your 8720MC

Cable Sizes

In the table below the appropriate variable frequency drive shielded
cable to use based on 150% overload capability and 25° C (77° F)
operating temperature is shown. The cable is shown in Figure 3.1.

For applications above 130 amps, use thick insulation lead wire, such
as RHW-2 or equal. Make sure you thread the four wires (U, V, W, and
ground) through a single, grounded, metal conduit.

1.5x Rated Continuous
Motor Current

VFD Cable Size

12 amps

#16 AWG

17 amps

#14 AWG

21 amps

#12 AWG

30 amps

#10 AWG

55 amps

#8 AWG

65 amps

#6 AWG

95 amps

#4 AWG

130 amps

#2 AWG