Rockwell Automation 8720MC High Performance Drives Installation Manual User Manual

Page 33

Advertising
background image

Publication 8720MC-IN001D-EN-P — December 2002

Installing Your 8720MC Drive

1-21

When mounting your active shunt module inside the enclosure,
follow these additional guidelines (refer to Figure 1.10 for an
example).

• Metal-clad modules can be mounted anywhere in the dirty zone,

but as close to the 8720MC as possible

• Shunt power wires can be run with motor power cables.
• Separate shunt power cables from other sensitive, low voltage

signal cables.

Figure 1.10
External Active Shunt Inside the Enclosure

C

C

D

VD

D

P1

P4

P5

TB1

BULLETIN 1336 BRAKING CHOPPER

FOR USE WITH

460 VAC A.F. DRIVES

CAT

1336-WB009 SER A

INPUT

750 VDC 9.0 ADC (RMS)

MADE IN U.S.A.

DC POWER

BRAKE ON

UL

®

LIS

TED 966X

IND

CONT E

Q

UL

®

LIS

TED 966X

IND

CONT E

Q

C

A

B P\N 74101-778-XX REV

VD

Dirty Wireway

Clean Wireway

Enclosure

Twisted conductors
(2 twists per foot) min. or
a shielded twisted pair.

Shield Clamp(s)

Route 24V dc I/O
Shielded Cable

Route Encoder/Analog/Registration
Shielded Cable

Motor Power
Shielded Cable

AC

Line Filter

8720MC
B Frame Chassis

Shield

Clamps

Note: Input AC components not

included in this figure.

Keep very dirty connections

as short as possible and

segregated (not in wireway)

150 mm (6.0 in.) of

clearance on all sides

of the shunt module

minimum

Allen-Bradley
Bulletin 1336-MOD-KBxxx
External Active Shunt Module

Advertising