Power dissipation specifications, External active shunt specifications – Rockwell Automation 8720MC High Performance Drives Installation Manual User Manual

Page 98

Advertising
background image

Publication 8720MC-IN001D-EN-P — December 2002

A-8

Specifications and Dimensions

Power Dissipation
Specifications

Use the following table to size an enclosure and calculate required
ventilation for your 8720MC system.

1

The open packaged drive ambient operating temperature is 50°C (122° F). The cabinet enclosure should be
designed to provide an operating temperature that does not exceed 50°C (122° F) in worst case ambient
conditions.

2

Drive rating is based on altitudes of 1000 meters (3000 feet) or less. If installed at a higher altitude, derate the
drive.

External Active Shunt
Specifications

The table below lists the ratings for the (optional) external active
shunt module (for use with the 8720MC-B021, -B027, -B034, -B042,
and -B048).

Catalog
Number
8720MC-

Base Derate
Amps

2

Drive Frame
Size

Heat
Dissipation
(Drive) Watts

1,2

Heat sink
Watts

1,2

Total Watts

1,2

380 - 480V ac or 750V dc Input Drives

B014

14

B

91

270

361

B021

21

B

103

394

497

B027

27

B

117

486

603

B034

34

B

140

628

768

B042

42

B

141

720

861

B048

48

B

141

820

961

D065

65

C

175

933

1108

D078

78

C

193

1110

1303

D097

97

D

361

1708

2069

D120

120

D

361

1708

2069

D149

149

D

426

1944

2307

D180

180

D

522

2664

3186

External Shunt
Catalog Number

Drive
Voltage
V ac

Ratings

Shipping
Weight
kg (lbs)

Bussmann

Replacement Fuse

Resistance
Range
Ohms

Peak
Power
kW

Peak
Current
Amps

Cont.
Power
Watts

1336-MOD-KB005

460

104.0

6

7.5

375

6.8 (15)

A60Q

1336-MOD-KB010

460

52.0

12

15

750

A60Q

1336-MOD-KB050

460

10.0

60

76

3750

33.8 (75)

A70QS35

Advertising