Connecting Input Power (Without an 8720MC-RPS)

These procedures assume you have mounted your 8720MC drive and
components and are ready to wire your AC input power.

To wire drive input power:

1. Prepare the incoming wires for attachment to the AC input

terminals by removing 10 mm (0.375 in.) of insulation.

2. Route the 3 phase power wires (R,S,T) to the TB1 connector. Refer

to figures 2.1 and 2.3 for the location of TB1.

3.

1

Refer to Appendix B for power wiring interconnect diagrams.

4. Gently pull on each wire to make sure it does not come out of its

terminal. Re-insert and tighten any lose wires.

5. Go to Connecting Motor Power.

IMPORTANT

When tightening screws to secure the wires, refer to
AC Drive Power Wiring Requirements for torque
values.

IMPORTANT

To ensure system performance, run wires and cables
in the wireway as established in Chapter 1.

IMPORTANT

Use caution not to nick, cut, or otherwise damage
the wire as you remove the insulation.

Insert this wire from the
3-phase supply:

Into this terminal
on the drive:

R

R (L1)

S

S (L2)

T

T (L3)

Bonded ground bar or
Terminal E on AC line filter

1