Grounded Distribution
Systems

The AC input drives are designed for use with conventional
three-phase supplies that are symmetrical with respect to ground.
Surge suppression devices are included to protect the drive from
lightning-induced over voltage between line and ground. For this
reason, use a neutral grounded system. The drive works with a
grounded phase, but you may want to use an isolation transformer to
provide a supply balanced with respect to ground.

Figure 3.3
Recommended 8720MC Grounding

Ungrounded Distribution
Systems

All 8720MC AC input drives are equipped with a metal oxide varistor
(MOV). The MOV provides voltage surge protection, phase-to-phase
as well as phase-to-ground, which is designed to meet IEEE 587. The
MOV circuit is designed for surge suppression only (transient line
protection), not continuous operation.

With ungrounded distribution systems, the phase-to-ground MOV
connection could become a continuous current path to ground. MOV
line-to-line and line-to-ground voltages should not exceed the input
voltage rating shown in Appendix A. Exceeding these values may
cause physical damage to the MOV.

R (L1)

S (L2)

T (L3)

PE

Ground Rod/Grid
or Building Structure Steel

Conduit/4-Wire Cable

U (T1)

V (T2)

W (T3)

PE/Gnd

TE

Shield

Motor Frame

PE

Ground per

Local Codes