External active shunt module, External active shunt module -20 – Rockwell Automation 8720MC High Performance Drives Installation Manual User Manual

Page 32

Advertising
background image

Publication 8720MC-IN001D-EN-P — December 2002

1-20

Installing Your 8720MC Drive

External Active Shunt Module

Observe the following guidelines when mounting your external active
shunt module (1336-MOD-KBxxx) outside the enclosure. Refer to
Figure 1.9 for an example.

• Mount circuit components and wiring in the very dirty zone or in

an external shielded enclosure (as shown in the figure below)

• Run shunt power and fan wiring inside metal conduit to minimize

the effects of EMI and RFI

• Keep unshielded wiring as short as possible

Figure 1.9
External Active Shunt Outside the Enclosure

C

C

D

VD

D

P1

P4

P5

TB1

VD

BULLETIN 1336 BRAKING CHOPPER

FOR USE WITH

460 VAC A.F. DRIVES

CAT

1336-WB009 SER A

INPUT

750 VDC 9.0 ADC (RMS)

MADE IN U.S.A.

DC POWER

BRAKE ON

UL

®

LIS

TED 966X

IND

CONT E

Q

UL

®

LIS

TED 966X

IND

CONT E

Q

C

A–B P\N 74101-778-XX REV

VD

Dirty Wireway

Clean Wireway

Customer-supplied

metal enclosure (optional)

150 mm (6.0 in.) of

clearance on all sides

of the shunt module

minimum

Metal
conduit

Enclosure

Twisted conductors

(2 twists per foot) min. or

a shielded twisted pair.

Allen-Bradley
Bulletin 1336-MOD-KBxxx
External Active Shunt Module

Shield Clamp(s)

Route 24V dc I/O
Shielded Cable

Route Encoder/Analog/Registration
Shielded Cable

Motor Power
Shielded Cable

AC

Line Filter

8720MC
B Frame Chassis

Shield

Clamps

Note: Input AC components not

included in this figure.

Keep very dirty connections as short as

possible and segregated (not in wireway)

Advertising