Publication 8720MC-IN001D-EN-P — December 2002

8720MC Connector Data

2-17

Digital output specifications are shown in the table below. Refer to
Figure 2.14 for the typical digital output configuration. Figure 2.14
shows the typical digital output connections. Use # 16 to #18 hook-up
wire, Alpha 3075 or 3077 or equal.

Figure 2.14
Typical Digital Output Connections

Relay Outputs

The 8720MC Drive has four discrete outputs in the form of normally
open dry relay contacts. The fault outputs from the 8720MC Drive are
supplied at terminal blocks. Fault outputs provide warning or fault
signals based on drive programming. The following values are the
contact ratings for the programmable relays:

Figure 2.15 shows a typical isolated relay output circuit. Use #16 to
#18 hook-up wire, Alpha 3075 or 3077 or equal.

Condition

Voltage

Amperage

On

Up to 40V dc

Up to 75 mA current limited

Off

N/A

less than 0.25 mA leakage

Optically isolated to 500V
6 outputs - P5-10 thru P5-12 and
P5-28 thru P5-30
P5-31 is external power

P5-31

P5-n

Customer

output device

+24V dc Output

External Power

Customer

+24V dc

power supply

-

+

+

-

Condition

Voltage

Amperage

On

Up to 250V ac

Up to 5A

On

Up to 30V dc

Up to 5A