Relay outputs, Relay outputs -17 – Rockwell Automation 8720MC High Performance Drives Installation Manual User Manual
Page 51

Publication 8720MC-IN001D-EN-P — December 2002
8720MC Connector Data
2-17
Digital output specifications are shown in the table below. Refer to
Figure 2.14 for the typical digital output configuration. Figure 2.14
shows the typical digital output connections. Use # 16 to #18 hook-up
wire, Alpha 3075 or 3077 or equal.
Figure 2.14
Typical Digital Output Connections
Relay Outputs
The 8720MC Drive has four discrete outputs in the form of normally
open dry relay contacts. The fault outputs from the 8720MC Drive are
supplied at terminal blocks. Fault outputs provide warning or fault
signals based on drive programming. The following values are the
contact ratings for the programmable relays:
Figure 2.15 shows a typical isolated relay output circuit. Use #16 to
#18 hook-up wire, Alpha 3075 or 3077 or equal.
Condition
Voltage
Amperage
On
Up to 40V dc
Up to 75 mA current limited
Off
N/A
less than 0.25 mA leakage
Optically isolated to 500V
6 outputs - P5-10 thru P5-12 and
P5-28 thru P5-30
P5-31 is external power
P5-31
P5-n
Customer
output device
+24V dc Output
External Power
Customer
+24V dc
power supply
-
+
+
-
Condition
Voltage
Amperage
On
Up to 250V ac
Up to 5A
On
Up to 30V dc
Up to 5A