Rockwell Automation 8720MC High Performance Drives Installation Manual User Manual

Page 27

Advertising
background image

Publication 8720MC-IN001D-EN-P — December 2002

Installing Your 8720MC Drive

1-15

• The clean zone (C) is beneath and left of the 8720MC and includes

the P1 and P4 connector wiring (grey wireway).

• One dirty zone (D) is right of the 8720MC and includes motor

power and the P5 connections (black wireway). Another dirty
zone is below and right of the 8720MC-RPS and includes fuses,
contactors, circuit breakers, and the VAC input to the AC (EMC)
line filter.

• The very dirty zone (VD) is beneath and right of the 8720MC and

includes the DC bus wiring, AC input from the line filter,
8720MC-RPS, line reactor, varistor, and harmonic filter. Shielded
cable is required only if the very dirty cables enter a wireway.

• The SERCOS fiber optic cables are immune to electrical noise.

Figure 1.6
Establishing Noise Zones (Common Bus Configuration with 8720MC-RPS)

1

For examples of shield clamp attachment, refer to the System Design for Control of Electrical Noise Reference
Manual
(publication GMC-RM001x-EN-P).

2

If necessary, the AC line filter may be moved ahead of the input contactors and fuses. However, it is important to
segregate the very dirty wiring between the filter and drives and keep as short as possible to prevent noise
coupling into susceptible circuits.

(1)

C

C

D

VD

D

C

D

REGENERATIVE POWER SUPPLY

REGENERATIVE POWER SUPPLY

8720

MC

RST PRG ENT

READY

READY

FAULT

FAULT

PROGRAM

PROGRAM

kW

kW

V

A

VD

VD

D

P1

P4

P5

TB1

8720MC
B Frame Chassis

Dirty Wireway

Clean Wireway

Route 24V dc I/O
Shielded Cable

Varistor

Dirty Wireway

8720MC
Regenerative
Power Supply
(8720MC-RPSxxx-BM-HV1)

Shield Clamp(s)

1

Route Encoder/Analog/Registration
Shielded Cable

Motor Power
Shielded Cable

Keep very dirty connections as short as

possible and segregated (not in wireway)

Line

Fuses

Contactors

Shield

Clamps

Circuit

Breaker

8720MC

Line Reactor

Harmonic

Filter

DC Bus /

≤ 2 m (78.7 in.)

AC

Line Filter

2