background image

Publication 8720MC-IN001D-EN-P — December 2002

2-20

8720MC Connector Data

Analog Outputs

The 8720MC includes two analog outputs (not supported on the
SERCOS models) that can be configured through software to represent
drive variables. Figure 2.17 shows the configuration of the analog
output. The following table provides a description of the analog
output.

Figure 2.17
Analog Output Configuration

The following table provides a description of the analog output
specifications.

SERCOS Connections

Two fiber-optic connectors (transmit and receive) are provided on the
drive. The table below lists SERCOS communication specifications.

50

0.01

µF

AOUT

IMPORTANT

Output values can vary during power-up until the
specified power supply voltage is reached.

Parameter

Description

Minimum

Maximum

Resolution

Number of states that the output signal is divided
into, which is 2

(to the number of bits)

.

12 Bits

Output
Current

Current capability of the output.

-20 mA

+20 mA

Output
Signal Range

Range of the output voltage.

-10V

+10V

Offset Error

Deviation when the output should be at 0V.

100 mV

Gain Error

Deviation of the transfer function from unity gain,
expressed in a percent of full scale.

5%

Bandwidth

Frequency response of the analog output

50 Hz

7.2 Khz (-3 db)

Specification

Description

Data Rates

2, 4, and 8 MBd

Node Addresses

00-99