Digital plug-ins – Rockwell Automation 2080 Micro800 Digital and Analog Plug-in Modules User Manual

Page 10

Advertising
background image

2

Rockwell Automation Publication 2080-UM004B-EN-E - December 2013

Chapter 1 Micro800 Plug-in Modules

Number of support for Micro800 plug-ins on the controllers are summarized in
the following table.

Digital Plug-ins

12/24V Digital Plug-ins — 2080-IQ4, 2080-IQ4OB4, 2080-IQ4OV4,
2080-OB4, 2080-OV4

These digital plug-in modules provide transistor outputs for switching a variety
of 12/24V DC voltages to field loads and for detecting 12/24V signals from field
devices.

2080-OF2

Analog

2-channel, Non-isolated unipolar voltage/current
analog output

2080-TC2

Specialty

2-channel, non-isolated thermocouple module

2080-RTD2

Specialty

2-channel, non-isolated RTD module

2080-MEMBAK-RTC

(1)

Specialty

Memory backup and high accuracy RTC

2080-TRIMPOT6

Specialty

6-channel trimpot analog input

2080-MOT-HSC

Specialty

High speed counter

2080-DNET20

Communication

20-node DeviceNet scanner

2080-SERIALISOL

Communication

RS232/485 isolated serial port

(1) 2080-MEMBAK-RTC is not supported on Micro820 controllers.

Plug-in Slots on Micro800 Controllers

Controller

Number of Plug-in Slots

Micro810

0

Micro820

2

Micro830

2 (10/16 points)
3 (24 points)
5 (48 points)

Micro850

3 (24 points)
5 (48 points)

ATTENTION: Removal and Insertion Under Power (RIUP) is not supported
on all Micro800 plug-in modules, except on the 2080-MEMBAK-RTC
module.

ATTENTION: Micro800 plug-in modules can be installed on any plug-in
slot on the controller, except for the 2080-MEMBAK-RTC module which
can only be installed on the leftmost plug-in slot.

Micro800 Plug-in Modules

Module

Type

Description

Advertising