Rockwell Automation 2080 Micro800 Digital and Analog Plug-in Modules User Manual

Page 68

Advertising
background image

60

Rockwell Automation Publication 2080-UM004B-EN-E - December 2013

Appendix A Specifications

Backplane power

3.3 VDC, 38 mA

Output current, resistive

2 A @ 5…30V DC
0.5 A @ 48V DC
0.22 A @ 125V DC
2 A @ 125V AC
2 A @ 240V AC

Output current, inductive

1.0 A steady state @ 5…28V DC
0.93 A steady state @ 30V DC
0.5 A steady state @ 48V DC
0.22 A steady state @ 125V DC
2.0 A steady state, 15 A make @ 125V AC, PF – cos

θ = 0.4

2.0 A steady state, 7.5 A make @ 240V AC, PF – cos

θ = 0.4

Output power, resistive, max

250 VA for 125V AC resistive loads
480 VA for 240V AC resistive loads
60 VA for 30V DC resistive loads
24 VA for 48V DC resistive loads
27.5 VA for 125V DC resistive loads

Pilot duty rating

C300, R150

Minimum load, per point

10 mA

Initial contact resistance of relay, max

30 m

Ω

Output delay time, max

10 ms ON or OFF

Relay Contact Ratings (0.35 power factor) – 2080-OW4I

Maximum Volts

Amperes

Amperes
Continuous

Volt-Amperes

Make

Break

Make

Break

120V AC

15 A

1.5 A

2.0 A

1800 VA

180 VA

240V AC

7.5 A

0.75 A

24V DC

1.0 A

28 VA

125V DC

0.22 A

Environmental Specifications – 2080-OW4I

Attribute

Value

Temperature, operating

IEC60068-2-1 (Test Ad, Operating Cold),
IEC60068-2-2, (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-20...65 °C (-4…149 °F)

Temperature, surrounding
air, max.

65 °C (149 °F)

Temperature, non-operating

IEC60068-2-1 (Test Ad, Operating Cold),
IEC60068-2-2, (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-40...85 °C (-40…185 °F)

Relative humidity

IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
5…95% noncondensing

Vibration

IEC 60068-2-6 (Test Fc, Operating):
2 g @ 10…500 Hz

Shock, operating

IEC 60068-2-27 (Test Ea, Unpackaged Shock):
10 g

General Specifications – 2080-OW4I Digital Relay Output Plug-in Module