Ra_encoderfdbk – Rockwell Automation 2080 Micro800 Digital and Analog Plug-in Modules User Manual

Page 44

Advertising
background image

36

Rockwell Automation Publication 2080-UM004B-EN-E - December 2013

Appendix 4 High Speed Counter – 2080-MOT-HSC

RA_EncoderFDBK

RA_HSCPlugIn: Input and Output Parameters

Parameter

Type

Data Type

Description

FBEN

INPUT

BOOL

Function block Enable input

SlotID

INPUT

UINT

Plug-in slot number.
Slot ID = 1…5 (starting with the far left slot 1.)

NoiseFilter

INPUT

USINT

00: No filter
01: 250 kHz
02: 200 kHz
03: 80 kHz
04: 40 kHz
05: 13.3 kHz
06: 10 kHz
07: 4 kHz
08: 2 kHz
09: 1 kHz
10: 500 Hz
11: 250 Hz
12: 125 Hz
13: 63.5 Hz
14: 31.25 Hz

HSCMode

INPUT

USINT

0, 2 , 4, 6, 8, 10, 12

Start

INPUT

BOOL

Start counter.

Stop

INPUT

BOOL

Stop the counter and clear “MaxDPos” and
“MaxDSpd” value.

FBENO

OUTPUT

BOOL

Function block Enable output.

IDCHeck

OUTPUT

BOOL

TRUE: HSC plug-in is at selected slot.
FALSE: Wrong plug-in or no plug-in at selected slot.

Initialized

OUTPUT

BOOL

TRUE: HSC plug-in initialization finished and ready
to execute.
FALSE: HSCplug-in initialization not yet finished.

Accumulator

OUTPUT

LINT

Accumulator value.

Rate

OUTPUT

Real

Current pulse rate. The rate calculation is based on
how many pulses have been counted every 10 ms.

RA_EncoderFDBK: Input and Output Parameters

Parameter

Type

Data
Type

Description

FBEN

INPUT

BOOL

Function block Enable input

SlotID

INPUT

UINT

Plug-in slot number.
Slot ID = 1…5 (starting with the far left slot 1)

HomePos

INPUT

REAL

Home position.
Same value indicated in MC_Home instruction.

RA_EncoderFDBK

FBEN

SlotID

HomePos

NoiseFilter

FBENO

IDCheck

EncMode

TrvPerRev

Initialized

CurrentPOS

CurrentSpd

Start
Stop

Accumulator

TpPosition

Direction

Advertising