Rockwell Automation Publication 2080-UM004B-EN-E - December 2013
55
DeviceNet Plug-in – 2080-DNET20 Appendix 5
4
MAC ID
5
Service
6…7
Class
8…9
Instance
10…115
Service Data (106 Bytes)
Explicit Message Response Format
Byte Offset
Contents
0
Status
1
Transaction ID
2
Size
3
Reserved
4
MAC ID
5
Service
Byte Offset
Contents
Request Data
0
Status
Can be read from UDFB status
6…115
ServiceData
Can be read from UDFB response data.
Response data shows CIP error Code.
Explicit Message Status Codes
Status Code
Description
0
Ignore transaction block (block empty).
1
Transaction completed successfully.
2
Transaction in progress (not ready).
4
Error – node offline
5
Error – DeviceNet port disabled/offline
6
Error – Transaction TXID unknown
7
Error – Duplicate TXID
9
Error – Scanner out of buffers
12
Error – Response data too large for block
14
Error – Invalid size specified
15
Error – Device timed out
16
Block queued.
17
Block allocated
18
Connection in progress
3, 8, 10, 11, 13, 19...255
Reserved
Explicit Message Request Format
Byte Offset