Rockwell Automation 2080 Micro800 Digital and Analog Plug-in Modules User Manual

Page 63

Advertising
background image

Rockwell Automation Publication 2080-UM004B-EN-E - December 2013

55

DeviceNet Plug-in – 2080-DNET20 Appendix 5

4

MAC ID

5

Service

6…7

Class

8…9

Instance

10…115

Service Data (106 Bytes)

Explicit Message Response Format

Byte Offset

Contents

0

Status

1

Transaction ID

2

Size

3

Reserved

4

MAC ID

5

Service

Byte Offset

Contents

Request Data

0

Status

Can be read from UDFB status

6…115

ServiceData

Can be read from UDFB response data.
Response data shows CIP error Code.

Explicit Message Status Codes

Status Code

Description

0

Ignore transaction block (block empty).

1

Transaction completed successfully.

2

Transaction in progress (not ready).

4

Error – node offline

5

Error – DeviceNet port disabled/offline

6

Error – Transaction TXID unknown

7

Error – Duplicate TXID

9

Error – Scanner out of buffers

12

Error – Response data too large for block

14

Error – Invalid size specified

15

Error – Device timed out

16

Block queued.

17

Block allocated

18

Connection in progress

3, 8, 10, 11, 13, 19...255

Reserved

Explicit Message Request Format

Byte Offset

Contents

Advertising