64

Rockwell Automation Publication 2080-UM004B-EN-E - December 2013

Appendix A Specifications

Specialty Plug-in Modules

Certifications – 2080-IF2, 2080-IF4, 2080-OF2

Certification (when
product is marked)

(1)

(1) See the Product Certification link at

http://www.rockwellautomation.com/products/certification/

for

Declarations of Conformity, Certificates, and other certification details.

Value

c-UL-us

UL Listed Industrial Control Equipment, certified for US and Canada.

See UL File E322657.

UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations,

certified for U.S. and Canada. See UL File E334470.

CE

European Union 2004/108/EC EMC Directive, compliant with:

EN 61326-1; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

European Union 2006/95/EC LVD, compliant with:

EN 61131-2; Programmable Controllers (Clause 11)

C-Tick

Australian Radiocommunications Act, compliant with:

AS/NZS CISPR 11; Industrial Emissions

Specifications – 2080-MEMBAK-RTC

Attribute

Value

Resolution READ_RTC()

1 s

Accuracy

± 5 sec/month @ 25 °C
± 9 sec/month@ -20…65 °C

Power off

Battery — 3.5 years from date of manufacture @ 25…65 °C, 2.5
years from date of manufacture @ 0 °C

Temperature, operating

IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock):
-20...65 °C (-4…149 °F)

Temperature, nonoperating

IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock):
-40...85 °C (-40…185 °F)

Relative humidity

IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
5…95% non-condensing

Altitude, operating

2000 m

IMPORTANT

Battery life does not include controller ON time. For example, if the
Controller is ON for 16 hours every day for 365 days, if the module starts
being used after 1 year of manufacturing, battery life is 8.5 years (1 year
initial time + 2.5 years of Off time out of 7.5 years).