C - error codes, Error codes, Troubleshooting – Rockwell Automation 2080 Micro800 Digital and Analog Plug-in Modules User Manual

Page 103: Error codes for micro800 plug-ins, Appendix c, Troubleshooting error codes for micro800 plug-ins, Appendix

Advertising
background image

Rockwell Automation Publication 2080-UM004B-EN-E - December 2013

95

Appendix

C

Error Codes

Troubleshooting

For troubleshooting your Micro800 controller system, see the User Manual for
your controller:

• Micro830 and Micro850 Programmable Controllers User Manual,

publication

2080-UM002

.

• Micro820 Programmable Controllers User Manual, publication

2080-UM005

.

Error Codes for Micro800
Plug-ins

This section lists possible error codes for your plug-in modules, as well as
recommended actions for recovery.

If an error persists after performing the recommended action, contact your local
Rockwell Automation technical support representative. For contact information,
go to

http://support.rockwellautomation.com/MySupport.asp

List of Error Codes for Micro800 Plug-ins

Error Code

Description

Recommended Action

For the following four error codes, z refers to the slot number of the plug-in module. If z = 0, then the slot number cannot be identified

0xF0Az

The plug-in I/O module has encountered an error
during operation.

Perform one of the following:

Check the condition and operation of the plug-in I/O module.

Cycle power to the Micro800 controller.

0xF0Bz

The plug-in I/O module configuration does not
match the actual I/O configuration detected.

Perform one of the following:

Correct the plug-in I/O module configuration in the user program to match

that of the actual hardware configuration.

Check the condition and operation of the plug-in I/O module.

Cycle power to the Micro800 controller.

Replace the plug-in I/O module.

0xF0Dz

A hardware error has occurred while power was
being applied to the plug-in module or the plug-in
module was removed.

Perform the following:

Correct the plug-in I/O module configuration in the user program.

Build and download the program using Connected Components Workbench.

Put the Micro800 controller into Run mode.

0xF0Ez

The plug-in I/O module configuration does not
match the actual I/O configuration detected.

Perform the following:

Correct the plug-in I/O module configuration in the user program.

Build and download the program using Connected Components Workbench.

Put the Micro800 controller into Run mode.

Advertising